Cable Construction
ConductorClass 5 flexible copper conductor according to BS EN 60228 (previously BS 6360)
InsulationEPR (Ethylene Propylene Rubber) Type EI4 according to BS EN 50363
SheathPCP (Polychloroprene) Type EM2 according to BS EN 50363

Dimensions

No. of CoresNominal Cross Sectional Area mm²Nominal Thickness of Insulation mmNominal Overall Diameter mmNominal Weight kg/kmA2 Glands
Brass
A2PL Gland
Plastic
11.50.85.85220/1620S
12.50.96.56720/1620S
1417.49220/1620S
1618.111920S20S
1101.29.818520S20S
1161.211.352582020
1251.413.33752520
1351.414.64852525
1501.617.26692525
1701.619.358923232
1951.822.211603232
11201.824.314363232
1150225.917484040
11852.229.721424040
12402.431.5269850S50S
13002.636.533485050S
14002.840.442935050
1500342.652625050
1630347.2679063S63S
210.88.19420S20S
21.50.8912020S20S
22.50.910.717320S20S
24112.32392020
26113.83132525
2101.218.65633225
2161.221.78303232
2251.425.812114040
310.88.7411720S20S
31.50.89.6814720S20S
32.50.911.481232020
34113.22972525
36114.783902525
3101.219.97053232
3161.223.3110313232
3251.427.715124040
3351.430.2190750S50S
3501.635.826515050S
3701.640.134845050
3951.846.4459463S63S
410.89.6314220S20S
41.50.810.6318020S20S
42.50.912.62602020
44114.63362525
46116.44492532
4101.221.88833232
4161.225.411384040
4251.430.7171450S50
4351.433.4220450S50
4501.639.6302950-
4701.644.9412163-
4951.851.9536163-
51.50.811.82062020L
52.50.9142972525
54116.24222525
56118.25673232
5101.22410104040
5161.228.214004040
5251.433.9209650S50
5351.437.227005050
5501.644373063S63S
71.50.815.133152525
72.50.917.64452532
121.50.818.24932532
122.50.921.47023232
191.50.822.17103232

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
Nominal Cross
Sectional Area mm²
Maximum Diameter of Wires in Conductor mmMaximum Resistance
of Conductor At 20ºC
Plain Wires ohms/km
10.2119.5
1.50.2613.3
2.50.267.98
40.314.95
60.313.3
100.411.91
160.411.21
250.410.78
350.410.554
500.410.386
700.510.272
950.510.206
1200.510.161
1500.510.129
1850.510.106
2400.510.0801
3000.510.0641
4000.510.0486
5000.610.0384
6300.610.0287

Current Carrying Capacity and Mass Supportable (1mm² to 2.5mm²)
Nominal Cross Sectional Area mm²Current Carrying CapacityMaximum Mass Supportable By Twin Flexible Cable
(See Regulations 522.7.2 and 559.6.1.5 of the 17th Edition of IEE Wiring Regulations)
kg
Single-Phase AC
Amps
Three-Phase AC
Amps
110105
1.516165
2.525205

Voltage Drop (1mm² to 2.5mm²)
Nominal Cross
Sectional Area mm²
DC or Single-Phase AC
mV/A/m
Three-Phase AC
mV/A/m
14640
1.53227
2.51916

Conductor Operating Temperature: 60°C

Current Carrying Capacity (4mm² and above)

Nominal Cross
Sectional Area mm²
60°C Conductor Operating Temperature85°C Conductor Operating Temperature **
Single-Phase AC or DCThree-Phase ACSingle-Phase AC or DCThree-Phase AC
1 Two Core Cable, With or Without Protective Conductor
Amps
2 Single Core Cables
Amps
1 Three Core, Four Core or Five Core Cable
Amps
1 Two Core Cable, With or Without Protective Conductor
Amps
2 Single Core Cables
Amps
1 Three Core, Four Core or Five Core Cable
Amps
430-2641-36
639-3453-47
1051-4773-64
1673-6399-86
2597-83131-114
35 -140102-192140
50-175124-240170
70-216158-297216
95-258192-354262
120-302222-414303
150 -347255-476348
185-394291-540397
240-471343-645467
300-541394-741537
400-644--885-
500-738--1017-
630-861--1190-

Ambient Temperature: 30°C
Conductor Operating Temperature: 60°C/85°C
The above table is for 60°C conductor operating temperature is in accordance with T4F1A of the 17th Edition of IEE Wiring Regulations.
** 85°C Table is in accordance with Table 4H2A of the 16th Edition of IEE Wiring Regulations.

 

The current ratings arranged are for cables in free air but may also be used for cables resting on the surface. If the cable is to be wound on a drum on load the ratings should be reduced in accordance with Note 2 below and for cables which may be covered, see Note 3.

Note 2: Flexible cables wound on reeling drums
The current ratings of cables used on reeling drums are to be reduced by the factors below:

A. Radial Type Drum
-Ventilated: 85%
-Unventilated: 75%

B. Ventilated Cylindrical Type Drum
-1 Layer of cable: 85%
-2 Layer of cable: 65%
-3 Layer of cable: 45%
-4 Layer of cable: 35%

A Radial Type Drum is where spiral layers of cable are accommodated between closely spaced fittings. If fitted with solid flanges the ratings given should be reduced and the drum is described as non-ventilated. If the flanges have suitable apertures the drum is described as ventilated.

A ventilated cylindrical cable drum is where layers of cable are accommodated between widely spaced flanges and the drum and end flanges have suitable ventilating apertures.

3. Where cable may be covered or coiled up whilst on load, or in air movement over the cable restricted, the current rating should be reduced.

It is not possible to specify the amount of reduction but the table of rating factors for reeling drums can be used as a a guide.

Voltage Drop (4mm² and above)

Nominal Cross
Sectional Area mm²
Two Core Cable, DC
mV/A/m
Two Core Cable,
Single-Phase AC
mV/A/m
1 Three Core, Four Core or Five Core Cable,
Three-Phase AC
mV/A/m
2 Single Core Cables,
Touching
DC
mV/A/m
Single-Phase AC
mV/A/m
4121210--
67.87.86.7--
104.64.64--
162.92.92.5--
251.81.80.1751.851.550.151.55----
35- ---1.10.151.151.311.310.211.32
50- ---0.830.1450.840.910.910.210.93
70----0.570.140.580.640.640.20.67
95----0.420.1350.440.490.490.1950.53
120----0.330.1350.360.380.380.190.43
150----0.270.130.30.310.310.190.36
185----0.220.130.260.250.250.190.32
240----0.170.130.210.190.1950.1850.27
300----0.1350.1250.1850.150.1550.180.24
400-------0.1150.120.1750.21
500-------0.090.0990.170.2
630-------0.0680.0790.170.185

Conductor Operating Temperature: 60°C
r = Resistive Component
x = Reactive Component
z = Impedance Value
* A larger voltage drop will result if the cables are spaced

 

De-Rating Factors

Ambient Temperature °C
3540455055
DE-RATING FACTOR0.910.820.710.580.41

power-accessories01

Our power cables have many accessories.

For more information, don’t hesitate to call us on 0121 508 6890 or get in touch via our Contact Page.